Electric Valve Actuator Sizing: Torque and RFQ Checklist

Size an electric valve actuator by defining valve torque, service factor, duty, operating time, power supply, controls and project acceptance records.

ZHONGYUE VALVE

11/16/20263 min read

Electric actuated ball valve for actuator torque sizing guide
Electric actuated ball valve for actuator torque sizing guide

An electric actuator should be selected from the actual valve operating torque and project conditions, not from valve size alone. An undersized unit may stall before the seat is fully engaged. An oversized unit can overload the stem, gearbox or seating parts if torque limits are not coordinated.

This procurement guide lists the information needed for an electric valve actuator RFQ. Final selection should be checked against the approved valve design, actuator data and project electrical specification.

Start with the valve torque requirement

Ask the valve supplier for the maximum required operating torque at the stated differential pressure and temperature. The calculation should identify the valve type, size, pressure class, seat material, stem and gearbox arrangement, direction of travel and service condition.

Ball valves may have break-to-open, running and end-to-close torque values. Gate and globe valves require thrust or torque based on stem geometry, differential pressure, packing friction and seating load. Butterfly valve torque can vary with disc position and flow direction. A single generic torque value is not sufficient for every valve type.

Define the service factor without hiding assumptions

The actuator output should include an agreed margin above the calculated valve requirement. The appropriate service factor depends on the application, frequency of operation, uncertainty in friction, ageing, deposits, temperature and project practice. State the selected factor in the sizing sheet rather than using an undocumented allowance.

Also verify that the maximum actuator output will not exceed the allowable torque or thrust of the valve stem, gearbox and seating system. Torque switches and mechanical stops must be set within the approved limits.

RFQ inputs that change actuator selection

Valve and process data

  • valve type, tag number, size, pressure class and end connection;

  • design and operating pressure/temperature;

  • maximum differential pressure during opening and closing;

  • fluid, solids content, corrosion concerns and expected deposits;

  • required fail or emergency position, if applicable;

  • maximum allowable stem torque or thrust.

Movement and operating time

  • quarter-turn, multi-turn or linear output;

  • required open and close time;

  • number of starts per hour and expected operating frequency;

  • modulating or on/off duty;

  • maximum travel and required position accuracy.

Electrical and environmental data

  • power supply voltage, phase and frequency;

  • control voltage and command signal;

  • ambient minimum and maximum temperature;

  • indoor or outdoor installation;

  • enclosure protection and corrosion-protection requirement;

  • hazardous-area classification and certification required by the project.

On/off duty vs modulating duty

An on/off actuator normally performs a limited number of full-stroke operations. A modulating actuator makes frequent positioning movements and must be selected for the required duty, starts per hour and control resolution. Do not assume an on/off actuator is suitable for throttling service.

For control applications, define the signal, dead band, positioning accuracy, feedback output and loss-of-signal action. Confirm whether the valve characteristic and actuator speed meet the process-control objective.

Controls and accessories to list separately

A complete actuator RFQ may include local open/close/stop controls, local/remote selector, position indication, torque and limit switches, space heater, terminal blocks, position transmitter, fieldbus interface, remote indication contacts and manual override. List required quantities and contact ratings.

If an integral starter or reversing contactor is required, define the motor protection, control scheme and interface responsibility. If the site uses a specific distributed control system, provide the protocol and I/O schedule before approval.

Mechanical interface checks

Confirm the mounting flange, drive sleeve, key or spline, stem dimensions, allowable side load and orientation. Review the combined weight and centre of gravity when the actuator is mounted on a vertical or extended bonnet. A support may be necessary for large or high-mounted assemblies.

For outdoor service, cable entries and drain/breather positions should suit the installed orientation. Manual override must remain accessible without interfering with nearby piping or structures.

Factory testing and document package

Define acceptance criteria before manufacturing. The requested package may include:

  • valve torque or thrust calculation and actuator sizing sheet;

  • actuator data sheet, wiring diagram and terminal plan;

  • general arrangement drawing with total weight;

  • motor and electrical component data;

  • functional test and travel-time record;

  • torque-switch and limit-switch setting record;

  • open/close indication and feedback verification;

  • enclosure or hazardous-area documentation when required by the purchase order.

Witness points should be listed in the approved inspection and test plan. Do not request a certification that is not required by the installation location or available product configuration.

Copyable electric actuator RFQ checklist

  • Valve tag, type, size, class and quantity

  • Maximum operating torque/thrust and allowable stem limit

  • Service factor and calculation assumptions

  • Open/close time and duty classification

  • Power and control supply

  • Control signal, feedback and communication protocol

  • Ambient temperature and enclosure requirement

  • Hazardous-area classification, if applicable

  • Manual override and mounting orientation

  • Required documents and inspection points

Request a coordinated valve and actuator review

Actuator sizing should be completed together with the selected valve and gearbox. Review the full operating envelope before approving the assembly. See Zhongyue Valve’s industrial valve product range or send your valve and actuator RFQ with the process, electrical and control requirements.

Zhongyue High Quality Valve Manufacturer

The products are exported to the United States, Europe, the Middle East, Southeast Asia, Russia and other countries and regions, reliable quality and reasonable price. Reliable quality and reasonable price are the basis of our continuous development.

Contact

Get in touch Please leave the questions you need to consult, later we will have a professional technical team to contact you.

Tel: +86 0577-28828932

WhatsApp/WeChat: +86 15658617888

© 2026 ZHONGYUE VALVE. All rights reserved.

QR code for Zhongyue Valve on WeChat
QR code for Zhongyue Valve on WeChat

WhatsApp

WeChat

QR code for Zhongyue Valve on WhatsApp
QR code for Zhongyue Valve on WhatsApp