Control Valve Bench Set vs. Signal Range: A FAT Checklist

Distinguish actuator bench set, positioner input, and instrument air supply. Use this control valve FAT checklist to compare supplier records.

11/24/20261 min read

Flanged control valve with a green pneumatic diaphragm actuator and positioner
Flanged control valve with a green pneumatic diaphragm actuator and positioner

A valve can reach both travel endpoints on an unloaded test bench and still lack the thrust needed in service. Start a factory acceptance test (FAT) by separating the spring bench set, the positioner command and the available instrument air. Each answers a different acceptance question.

Three ranges that belong in separate RFQ fields

  • Actuator bench set: The manufacturer's specified loading-pressure range associated with a defined actuator travel under its bench conditions. Record the spring, travel, units and test configuration.

  • Positioner input: The electrical, digital or pneumatic command accepted by the configured positioner. For a 4–20 mA loop, record command direction, travel limits and what the device does on loss of signal.

  • Air supply: The pressure available at the assembly, including the minimum during operation. Confirm the regulator setting and the permitted pressure limits of each component separately.

Ask for a FAT record tied to the valve tag

  1. Match the valve tag, actuator model, spring identification, positioner and drawing revision to the approved datasheet. Confirm the rated stroke and any travel stops.

  2. Record the test setup, gauge identification and observed loading-pressure endpoints using the actuator manufacturer's instructions. State whether the actuator was uncoupled and whether process forces were simulated.

  3. On the complete assembly, record command and measured travel at agreed points in both directions. Record fail response for each specified loss scenario. Document any overshoot, deadband or repeatability limit only against agreed criteria.

  4. Review calculated thrust at the minimum available air supply and specified differential pressure. A travel test under no process load cannot qualify shutoff or replace a specified seat leakage test.

What to send with the enquiry

Supply the valve tag and quantity, medium, pressure and temperature, operating and shutoff differential pressure, required fail position, minimum and maximum air supply, command type and FAT acceptance criteria. Ask the bidder to identify deviations before purchase. Use the approved assembly instructions for any adjustment.

See our related valve product page and related selection guide. Contact our team for an RFQ review.

Zhongyue High Quality Valve Manufacturer

The products are exported to the United States, Europe, the Middle East, Southeast Asia, Russia and other countries and regions, reliable quality and reasonable price. Reliable quality and reasonable price are the basis of our continuous development.

Contact

Get in touch Please leave the questions you need to consult, later we will have a professional technical team to contact you.

Tel: +86 0577-28828932

WhatsApp/WeChat: +86 15658617888

© 2026 ZHONGYUE VALVE. All rights reserved.

QR code for Zhongyue Valve on WeChat
QR code for Zhongyue Valve on WeChat

WhatsApp

WeChat

QR code for Zhongyue Valve on WhatsApp
QR code for Zhongyue Valve on WhatsApp